| Hazard Definition | Flammable gases, vapors, or liquids may be present under normal operating conditions or frequently during maintenance. | Flammable gases, vapors, or liquids are not normally present, but may occur because of abnormal operation, leakage, or equipment failure. | Zone 0: explosive gas atmosphere is present continuously, for long periods, or frequently. Zone 1: likely to occur occasionally during normal operation. | Explosive gas atmosphere is not likely during normal operation, but may exist for a short period if it occurs. | Obtain the site hazardous-area classification before selecting the motor, terminal box, controls, and fan assembly. |
| Common Protection Concept | Equipment must be suitable for frequent exposure to the classified atmosphere and designed to prevent ignition from internal or external sources. | Equipment is generally designed to prevent ignition under normal operation and specified abnormal conditions. | Zone 0 typically requires the highest equipment protection level; Zone 1 requires equipment suitable for frequent hazardous-gas exposure. | Equipment is designed for infrequent or short-duration exposure to an explosive atmosphere. | Confirm the complete protection method, such as flameproof, increased safety, pressurization, or another approved method—not only the marketing term “explosion-proof.” |
| Gas or Vapor Grouping | Class I groups are traditionally identified as A, B, C, and D. Group A covers acetylene; Group B includes gases such as hydrogen; Groups C and D cover progressively less severe gas hazards. | Uses the same Class I gas-group structure. The selected equipment must match the specific gas group stated for the installation. | IEC gas groups are IIA, IIB, and IIC, with IIC representing the most demanding gas subgroup. Grouping is not automatically identical to NEC group letters. | The fan and motor must be suitable for the applicable IIA, IIB, or IIC gas group shown on the certificate and nameplate. | Ask for the exact gas group, not a generic “gas-safe” statement. Verify that the fan, motor, cable glands, and accessories share compatible ratings. |
| Temperature Classification | Equipment temperature codes commonly range from T1 to T6. T6 has the lowest permitted maximum surface temperature and is generally the most restrictive. | The maximum surface temperature must remain below the ignition temperature of the hazardous material under the installation conditions. | IEC temperature classes T1–T6 are widely used; T1 permits up to 450°C, while T6 permits up to 85°C, subject to the applicable certification conditions. | The selected T-class must be equal to or more stringent than the hazardous gas or vapor requirement. | Compare the certified maximum surface temperature with the auto-ignition temperature of the process gas, including expected ambient-temperature effects. |
| Typical Area Relationship | Division 1 is broadly comparable in hazard frequency to Zone 0 or Zone 1, but the classifications are not direct legal equivalents. | Division 2 is broadly comparable to Zone 2 in many applications, but the final selection must follow local codes and the project certification basis. | Zone classification is based primarily on the probability and duration of an explosive atmosphere, rather than the NEC division terminology. | Zone 2 equipment may not automatically be acceptable for Zone 1 or Division 1 installations. | Do not convert divisions and zones without review by the project engineer, authority having jurisdiction, or local certification body. |
| Certification Documentation | Documentation should identify the applicable national electrical requirements, product construction, environmental limits, installation conditions, and approved hazardous-location ratings. | Review the certificate or listing information for Division 2 suitability, gas group, temperature code, enclosure type, and permitted installation methods. | IECEx documentation normally includes a certificate number, protection concept, equipment protection level, gas group, temperature class, and special conditions of use where applicable. | Confirm that the certificate explicitly covers Zone 2 and the selected protection level, ambient range, and installation arrangement. | Request the certificate, technical schedule, installation manual, dimensional drawing, wiring diagram, and routine-test records before purchase. |
| Motor and Fan Construction | The motor enclosure, shaft seals, bearings, terminal compartment, and fan materials must prevent ignition and withstand the classified environment. | The design should address ignition risks from arcing, overheating, friction, loose electrical connections, and abnormal operating conditions. | Construction must match the certified protection concept and may require controlled clearances, certified cable entries, and specified fasteners. | Even where the risk is lower, the motor and fan must remain within the certificate’s electrical, thermal, and mechanical limits. | Check impeller-to-housing clearance, anti-static or spark-resistant materials where required, bearing temperature, vibration limits, and motor overload protection. |
| Electrical Supply and Controls | Starters, switches, variable-frequency drives, sensors, junction boxes, and cable systems must also be approved for the classified location or installed outside it. | Control equipment may be installed in the hazardous area only when its ratings and wiring methods are appropriate for Division 2. | All associated apparatus, cable glands, and entry systems must be compatible with the zone, protection concept, gas group, and temperature class. | Verify whether the control panel and variable-speed drive are suitable for Zone 2 or must be located in a safe area. | Evaluate the entire power train as one system; a compliant motor cannot compensate for non-compliant controls or cable entries. |
| Environmental Performance | Selection must consider ambient temperature, humidity, corrosive gases, ingress protection, altitude, and installation outdoors or indoors. | The enclosure and coating system must tolerate the site environment while maintaining the certified protection performance. | Certificates may specify an ambient range, ingress protection level, ultraviolet resistance, corrosion restrictions, or special installation conditions. | Zone 2 suitability does not remove the need to verify environmental and mechanical ratings. | Match the fan’s IP rating, corrosion protection, ambient range, airflow duty, noise level, and vibration performance to the site specification. |
| Recommended Procurement Evidence | Hazardous-area rating, certificate or listing, installation instructions, motor data, test records, and evidence of compatibility with the local electrical code. | Division rating, gas group, temperature code, enclosure details, wiring method, and documentation for abnormal-condition operation. | IECEx certificate, marking details, equipment protection level, gas group, temperature class, ambient range, and special conditions of use. | Zone 2 certificate details, protection level, electrical limits, and confirmation that accessories are covered by the certification basis. | Use a compliance matrix covering hazardous area, gas group, temperature class, airflow, pressure, motor power, voltage, frequency, enclosure, and documentation. |